ESBE VRG132 mixing valve:

————————

Pressure class

PN10

Torque (at nominal pressure)

DN15-32: < 3 Nm, DN40-50: < 50 Nm

Leakrate in % of flow

Mixing: <0,05%; Diverting: <0,02%

Working pressure

1 MPa

Max. Differential pressure drop, Mixing

100 kPa

Max. Differential pressure drop, Diverting

200 kPa

Close off pressure

200 kPa

Rangeability Kv/Kv min, A-AB

100

Media, Heating water

in accordance with VDI2035

Media, Water/Glycol mixtures

max. 50 %

Media, Water/Ethanol mixtures

max. 28 %

Media temperature, max. continuosly

+110 °C

Media temperature, max. temporarily

+130 °C

Media temperature, min.

-10 °C

Material, Valve body

Dezincification resistant brass, DZR

ESBE ARA 639

————————

ESBE ARA 639 Power supply

24±10% V AC/DC, 50/60Hz

ESBE ARA 639 Enclosure rating

IP41

ESBE ARA 639 Running time

adjustable 15, 30, 60, 120 seconds

ESBE ARA 639 Rating auxiliary switch

6(3) A 250 V AC

ESBE ARA 639 Weight

0,4 kg

ESBE ARA 639 Ambient temperature, max.

+55 °C

ESBE ARA 639 Ambient temperature, min.:

-5 °C

ESBE ARA 641

————————

ESBE ARA 641 Power supply

230 ± 10% V AC, 50 Hz

ESBE ARA 641 Power consumption

230V: 5 VA

ESBE ARA 641 Torque

6 nm

ESBE ARA 641 Running time 90° [s]

30

ESBE ARA 641 Ambient temperature, max.

+55 °C

ESBE ARA 641 Ambient temperature, min.

-5 °C

ESBE ARA 641 Rating auxiliary switch

6(3) A 250 V AC

ESBE ARA 641 Enclosure rating

IP41

Product code: NLK-HP-B-SS-100M230V | NLK-HP-B-SS-100M24V Categories: ,

You may also like…

  • Nolsen HP-B-SS-100 heat center
    751  (inc VAT)

    Nolsen is a pre-assembled compact heat center for heat pump systems with high technical specification.

    The main unit of the heat center is a stainless steel buffer tank with capacity of 100 liter, which is specially developed for heat pump heating/cooling system.

    Components of Nolsen heat center
    – Stainless Steel buffer tank (SUS304)
    – 35 mm stainless steel pre-assembled pipe system

    Primary side
    – Microbubble separator
    – Magnetic dirt separator
    – Change-over valve with rotary actuator
    – 5/4″” ball valves
    – Automata air vent
    – Safety group

    Direct circuit
    – Pre-assembled pipe system
    – Circulator

    Mixed circuit
    – Pre-assembled pipe system
    – Circulator
    – Mixing valve with 24V or 230V rotary actuator